PHOENIX CONTACT PLC-RSC-230UC-21 ( 2966207 )
PHOENIX CONTACT PLC-RSC-230UC-21 PLC-INTERFACE, consisting of basic terminal block PLC-BSC…/21 with screw connection.
PLC-INTERFACE, consisting of basic terminal block PLC-BSC…/21 with screw connection and plug-in miniature relay with power contact, for assembly on DIN rail NS 35/7,5, 1 changeover contact, input voltage 230 V AC/220 V DC
| PHOENIX CONTACT PLC-RSC-230UC-21 | |
|---|---|
| Notes on operation | Separating plate PLC-ATP must be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC… or FBST 500…. |
| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer’s declaration in the download area |
| Product properties | |
|---|---|
| Product type | Relay Module |
| Application | Universal |
| Operating mode | 100% operating factor |
| Mechanical service life | 2x 107 cycles |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 3 |
| Electrical properties | |
|---|---|
| Maximum power dissipation for nominal condition | 0.74 W |
| Test voltage Winding/contact | 4 kV AC (50 Hz, 1 min., winding/contact) |
| Input data | |
|---|---|
| Coil side | |
| Coil side | Nominal input voltage UN 220 V DC |
| Input voltage range | 179.4 V AC … 264.5 V AC (20 °C) 171.6 V DC … 253 V DC (20 °C) |
| Typical input current at UN | 3.2 mA (at UN = 230 V AC) 3 mA (at UN = 220 V DC) |
| Typical response time | 7 ms |
| Typical release time | 15 ms |
| Protective circuit | Bridge rectifier; Bridge rectifier |
| Operating voltage display | Yellow LED |