SCHMERSAL 2356 (24-230VAC/DC)
SCHMERSAL 2356 SAFETY RELAY
- Monitoring of BNS range magnetic safety sensors
- 3 safety contacts, STOP 0
- 2 Signalling outputs
| ORDERING DATA | |
|---|---|
| Note (Delivery capacity) | Not available! |
| Product type description | AES 2356 UE: 24…230V AC/DC |
| Article number (order number) | 101181683 |
| EAN (European Article Number) | 4030661323145 |
| eCl@ss number, version 12.0 | 27-37-18-19 |
| eCl@ss number, version 11.0 | 27-37-18-19 |
| eCl@ss number, version 9.0 | 27-37-18-19 |
| ETIM number, version 7.0 | EC001449 |
| ETIM number, version 6.0 | EC001449 |
| Available until | 01.12.2021 |
| APPROVALS – STANDARDS | |
|---|---|
| Certificates | BG cULus EAC |
| GENERAL DATA | |
|---|---|
| Standards | BG-GS-ET-14 BG-GS-ET-20 EN IEC 62061 EN IEC 60947-5-1 EN IEC 60947-5-3 EN IEC 60947-5-5 EN IEC 61508 EN IEC 60204-1 EN IEC 60947-1 |
| Climatic stress | BG-GS-ET-14 IEC 60947-5-3 |
| Enclosure material | Glass-fibre, reinforced thermoplastic |
| Material of the contacts, electrical | Ag-Ni 10 and 0.2 µm gold-plated |
| Gross weight | 342 g |
| GENERAL DATA – FEATURES | |
|---|---|
| Stop-Category | 0 |
| Wire breakage detection | Yes |
| Cross-circuit detection | Yes |
| Feedback circuit | Yes |
| Automatic reset function | Yes |
| Start-up test | Yes |
| Reset after disconnection of supply voltage | Yes |
| Integral system diagnostics, status | Yes |
| Number of LEDs | 1 |
| Number of normally closed (NC) | 2 |
| Number of normally open (NO) | 2 |
| Number of undelayed semi-conductor outputs with signaling function | 2 |
| Number of safety contacts | 3 |
| Number of signalling outputs | 2 |
| Safety classification | |
| Standards | EN ISO 13849-1 EN IEC 61508 |
| Safety classification – Relay outputs | |
| Performance Level, up to | d |
| Category | 3 |
| PFH value | 1.00 x 10⁻⁷ /h |
| Notice | for max. 50,000 switching cycles/year and max. 80% contact load |
| Safety Integrity Level (SIL), suitable for applications in | 2 |
| Mission time | 20 Year(s) |
| MECHANICAL DATA | |
|---|---|
| Mechanical life, minimum | 20,000,000 Operations |
| Mounting | Snaps onto standard DIN rail to EN 60715 |
| MECHANICAL DATA – CONNECTION TECHNIQUE | |
|---|---|
| Termination | rigid or flexibleScrew terminals M20 x 1.5 |
| Terminal designations | IEC/EN 60947-1 |
| Cable section, minimum | 0.25 mm² |
| Cable section, maximum | 2.5 mm² |
| Tightening torque of Clips | 0.6 Nm |
| MECHANICAL DATA – DIMENSIONS | |
|---|---|
| Width | 45 mm |
| Height | 100 mm |
| Depth | 121 mm |
| AMBIENT CONDITIONS | |
|---|---|
| Degree of protection of the enclosure | IP40 |
| Degree of protection of the mounting space | IP54 |
| Degree of protection of clips or terminals | IP20 |
| Ambient temperature, minimum | +0 °C |
| Ambient temperature, maximum | +55 °C |
| Storage and transport temperature, minimum | -25 °C |
| Storage and transport temperature, maximum | +70 °C |
| Resistance to vibrations | 10…55 Hz, Amplitude 0.35 mm, ± 15 % |
| Restistance to shock | 30 g / 11 ms |
| AMBIENT CONDITIONS – INSULATION VALUES | |
|---|---|
| Rated impulse withstand voltage Uimp | 4 kV |
| Overvoltage category | III |
| Degree of pollution | 2 |