SCHMERSAL AES 2135 (24-230V AC/DC)
SCHMERSAL SAFETY RELAY
- Monitoring of BNS range magnetic safety sensors
- 1 safety contact, STOP 0
- 2 Signalling outputs
| GENERAL DATA | |
|---|---|
| Enclosure material | Glass-fibre, reinforced thermoplastic |
| Material of the contacts, electrical | Ag-Ni, Au |
| Gross weight | 280 g |
| GENERAL DATA – FEATURES | |
|---|---|
| Stop-Category | 0 |
| Wire breakage detection | Yes |
| Cross-circuit detection | Yes |
| Automatic reset function | Yes |
| Reset after disconnection of supply voltage | Yes |
| Integral system diagnostics, status | Yes |
| Number of LEDs | 1 |
| Number of normally closed (NC) | 2 |
| Number of normally open (NO) | 1 |
| Number of undelayed semi-conductor outputs with signaling function | 2 |
| Number of safety contacts | 1 |
| Number of signalling outputs | 2 |
| Safety classification | |
| Standards | EN ISO 13849-1 EN IEC 61508 |
| Safety classification – Relay outputs | |
| Performance Level, up to | d |
| Category | 3 |
| PFH value | 1.00 x 10⁻⁷ /h |
| Safety Integrity Level (SIL), suitable for applications in | 2 |
| Mission time | 20 Year(s) |
| MECHANICAL DATA | |
|---|---|
| Mechanical life, minimum | 50,000,000 Operations |
| Mounting | Snaps onto standard DIN rail to EN 60715 |
Add comment
Comments